Bathroom Zones Explained: Which IP Rated Lights Go Where (UK)

9 min read

Modern UK bathroom with a walk-in shower and sealed white LED downlights in the ceiling, lit in warm white

The short answer

Bathroom zones mark how close equipment is to water. Zone 0 is inside the bath or shower tray, zone 1 is directly above it to 2.25m from the floor (or the shower head if higher), and zone 2 extends 0.6m beyond that. Lights in zones 1 and 2 need at least IPX4, IPX5 where water jets are used. Choose IP65 directly over a shower and IP44 elsewhere, with 30mA RCD protection.

Key takeaways

  • Zone 0 is inside the bath or tray, zone 1 is above it to 2.25m, zone 2 is 0.6m beyond zone 1.
  • Zones 1 and 2 need at least IPX4 (IPX5 where water jets are used); IP65 directly over a shower gives you margin.
  • Outside the zones there is no set IP rating, but IP44 is the sensible choice for steam.
  • Wall switches go outside the zones; use a ceiling pull cord inside the room.
  • All bathroom circuits need 30mA RCD protection, and most bathroom electrical work is notifiable under Part P.
On this page
  1. Bathroom zones in one minute
  2. Where each bathroom zone starts and stops
  3. What IP rating do bathroom lights need?
  4. Can you put downlights over a shower?
  5. Do you need 12V lights in a bathroom?
  6. Bathroom light switches and pull cords
  7. RCD protection and who can do the work
  8. Does a light outside the zones still need an IP rating?
  9. EICR comments and the "arm's reach" question
  10. How to choose bathroom lights, step by step
  11. If you want the short version
  12. Common questions

Bathroom zones in one minute

Bathroom zones are the areas around a bath or shower where water is most likely to reach electrical equipment. The UK wiring rules, BS 7671, split a bathroom into zone 0, zone 1, zone 2 and the space outside the zones. The closer a light is to the water, the higher its IP rating must be and the stricter the rules on voltage and switching. Get the zone right first, then pick the light.

Zone Where it is Minimum IP rating for a light What usually goes there
Zone 0 Inside the bath or shower tray, where water collects IPX7 Only SELV equipment (12V AC or 30V DC at most) made for immersion, with the transformer outside the zones
Zone 1 Directly above the bath or shower tray, up to 2.25m from the floor, or higher if the fixed shower head is higher IPX4, or IPX5 where water jets are used for cleaning Sealed downlights and ceiling lights made for zone 1
Zone 2 0.6m beyond the edge of zone 1, up to the same height, and round the washbasin if it sits in that space IPX4, or IPX5 where water jets are used IP44 ceiling lights, spotlights and mirror lights
Outside the zones Everywhere else in the room No set IP rating in the rules, but IP44 is the sensible choice for steam and condensation Main ceiling lights, wall lights, extractor fan lights

The first digit of an IP rating is protection against solid objects and dust; the second is protection against water. An X means the solid digit was not tested. So IP44 and IPX4 both meet "at least IPX4" for water, and IP65 goes well beyond it.

Where each bathroom zone starts and stops

The diagram shows a bath against a wall, seen from the side. A shower tray works the same way: zone 0 is inside the tray, zone 1 is the column of space above it.

Side view of a bathroom: zone 0 inside the bath, zone 1 above the bath up to 2.25 metres, zone 2 extending 0.6 metres beyond, and the rest of the room outside the zones Zone 0 inside the bath, IPX7 Zone 1 Zone 2 Outside the zones IP44 still advised IPX4 or better IPX4 shower head ceiling light 2.25m above the floor 0.6m ceiling floor
Zone 1 rises from the bath to 2.25m above the floor, or to the fixed shower head if that is higher. Zone 2 adds 0.6m around it. A ceiling light above the 2.25m line can sit outside zone 1 on paper, which is why the real heights in your room matter.

Showers without a tray and wet rooms

Where there is no tray, zone 1 is measured from the fixed water outlet: it reaches 1.2m out from the shower head in every direction across the floor. That makes zone 1 much larger in a wet room, and there may be no separate zone 2. Measure from the outlet before you place lights, switches or a mirror.

The washbasin

A basin on its own does not create a zone. If it sits within 0.6m of the bath or shower, it falls inside zone 2, so a mirror light or spotlight above it needs at least IPX4.

What IP rating do bathroom lights need?

For most homes the answer is simple: IP44 or better anywhere near the bath or shower, IP65 directly over a shower. The rules set IPX4 as the minimum in zones 1 and 2, but IP65 gives you margin for steam, splashing and the shower head that ends up pointing at the ceiling.

Rating What it means for water Good for
IP20 No water protection Outside the zones only, in a well ventilated room; avoid in bathrooms if you can
IP44 Splashing from any direction Zone 2 and outside the zones; zone 1 where the fitting is made for it
IP65 Dust tight and protected against water jets Zone 1 over a bath or shower, wet rooms, rooms cleaned with a hose or jet
IP67 Short, temporary immersion Zone 0 only with SELV and the right fitting; also low level and plinth lights

Look at where the rating applies. Some downlights are IP65 from the front only. That is what matters in a bathroom, because the front faces the room and the back sits in the ceiling void. Our Calipso 7W fire rated downlight is one of these: IP65 from the front, with a 65mm cut-out.

Get this right

Read the IP rating and the zone on the product, not just the word "bathroom" in the title. A fitting can be IP44 and still be marked for zone 2 and outside the zones only. Our Saxby Knight 3 spot bar, for example, is IP44 and listed for zone 2 and outside the zones, so it belongs over the basin or in the middle of the room, not directly over the shower.

Can you put downlights over a shower?

Yes, if the downlight is rated for the zone. Over a shower or a bath you are usually in zone 1, so choose a sealed downlight with at least IPX4, and IP65 if water may hit it directly. Our IP65 fire rated downlights are made for this: the fire rated downlight range includes IP65 models that can also go under insulation in a loft or ceiling void.

Two things people miss:

  • Fire rating still applies. If there is a room or a loft above, the ceiling may need its fire resistance restoring around each hole. A fire rated IP65 downlight solves both problems in one fitting.
  • The height can change the zone. If your ceiling is above 2.25m and the shower head is lower, the ceiling may be outside zone 1. Most electricians still fit IP65 there, because steam rises and a new, higher shower head would move the boundary up.

Do you need 12V lights in a bathroom?

Not usually. Mains (230V) lights are allowed in zones 1 and 2 if they have the right IP rating and are made for the zone. SELV (safety extra low voltage, usually 12V from a safety transformer) is required in zone 0, and some people still choose it near the bath. If you do, the transformer or driver must sit outside the zones, somewhere you can reach it later, never buried behind tiles.

Old 12V MR16 halogen downlights are common in bathrooms. If you swap them for LED, the transformer often needs changing too, or the new lamps may flicker. Our guide explains why:why LED lights flicker, buzz or glow.

Bathroom light switches and pull cords

A standard wall switch must be outside the zones, in practice usually outside the door or at least well away from the bath and shower. Inside the room, the usual answer is a ceiling pull cord switch. The cord is insulating, so you can pull it with wet hands while the switch itself sits on the ceiling, out of reach of water.

  • Pull cords may hang into the zones, because only the cord is there.
  • Shaver sockets made to the right standard can go in zone 2. Ordinary socket outlets have to be well clear of zone 1, and how far is something your electrician will measure.
  • Dimmers and smart switches follow the same rule as wall switches: outside the zones.

RCD protection and who can do the work

All circuits in a room with a bath or shower need protecting by a 30mA RCD. Many older homes have this already in the consumer unit; some do not. Our Saxby bathroom fittings say the same thing on their spec tables: fit by a qualified electrician, with a 30mA RCD in a room containing a bath or shower.

In England and Wales most electrical work in a bathroom is notifiable under Part P of the Building Regulations. Use a registered electrician who can certify it. Swapping a lamp in an existing fitting is fine to do yourself; adding or moving a light, switch or circuit in a bathroom is not a DIY job.

Safety: when to call an electrician

Call an electrician to add, move or replace any fixed light in a bathroom, to fit a pull cord or fan, to check RCD protection, or if a fitting has water inside it, trips the RCD or shows rust or scorch marks. Turn the circuit off at the consumer unit before you change even a lamp, and never touch a bathroom fitting with wet hands.

Does a light outside the zones still need an IP rating?

The rules do not set one outside the zones, but steam does not read the rules. Condensation forms on the coldest surface, which is often the ceiling and the light fitting. For a main ceiling light in a bathroom, choose IP44. An IP20 fitting can work in a large, well ventilated bathroom with a strong extractor, but it is the first thing to fail in a small shower room.

The same thinking applies to an en suite with no window, a utility room with a shower tray, and the wall next to a steam shower. When in doubt, go one rating higher.

EICR comments and the "arm's reach" question

Electricians doing an EICR (electrical installation condition report) sometimes flag a light or switch in a bathroom that a person could touch while standing in the bath. If yours has been flagged, the fix is usually one of these: move the switch outside the room or swap it for a pull cord, replace an IP20 light with an IP44 or IP65 one, or add RCD protection. Ask the electrician which observation applies and what they recommend; codes on an EICR are their professional judgement, so they are the best person to explain them.

How to choose bathroom lights, step by step

  1. Measure the room: ceiling height, shower head height, the edge of the bath or tray, and 0.6m beyond it.
  2. Mark zones 0, 1 and 2 on a sketch. For a wet room, draw 1.2m from the shower outlet.
  3. Choose IP65 for anything directly over the bath or shower, and IP44 or better everywhere else.
  4. Check fire rating if there is a room or loft above. A fire rated IP65 downlight covers both.
  5. Pick the colour: 3000K for a warm, relaxing room, 4000K for a crisp light for shaving and make-up. A colour switchable downlight lets you decide after fitting.
  6. Plan the switching: a pull cord inside, or a switch outside the door.
  7. Book a registered electrician and confirm the circuit has 30mA RCD protection.

For the colour question in more depth, our LED downlights come in 2700K, 3000K and 4000K, and several switch between colours.

For installers

  • Calipso 7W fire rated: IP65 from the front, 65mm cut-out, rated 30, 60 and 90 minutes, switchable 2700K or 4000K, Triac dimmable, push-in loop-in/loop-out terminals, can be covered with insulation.
  • 12W fire rated tri-colour: IP65, over 1350 lm, 3000K, 4000K or 6000K by double-clicking the switch, 90 minute fire rating, cut-out 70 to 75mm.
  • Altair 8W twin pack: IP65, 600 lm, 90 minute fire rating, colour set on the housing or by toggling the switch.
  • Saxby Knight 3 spot bar: IP44, zone 2 and outside the zones, class 2 (no earth needed), keep spots 0.2m from the lit surface.

If you want the short version

Zone 0 is inside the bath, zone 1 is above it to 2.25m, zone 2 is 0.6m beyond that. Use IP65 over the bath or shower, IP44 everywhere else in the room, switches outside the zones or a pull cord, and 30mA RCD protection on every circuit. Measure your own room, check each fitting's zone marking, and leave the wiring to a registered electrician. Browse our bathroom LED lights and IP65 fire rated downlights to match each zone.

Products that help

See all Bathroom LED Lights · See all LED Fire Rated Spot Downlight · See all LED Downlights · IP Rating Chart: IP44, IP65, IP67 and IP68 Explained for Lights · Fire Rated Downlights: Do You Need Them? UK Rules in Plain English · How Many Downlights Do I Need? Spacing, Lumens and a Room-by-Room Table

Common questions

What are the bathroom zones?

Zone 0 is inside the bath or shower tray. Zone 1 is the space directly above it up to 2.25m from the floor, or higher if the fixed shower head is higher. Zone 2 extends 0.6m beyond zone 1, and the rest of the room is outside the zones.

What IP rating do I need for bathroom lights?

At least IPX4 in zones 1 and 2, or IPX5 where water jets are used for cleaning, and IPX7 in zone 0. In practice choose IP65 directly over a bath or shower and IP44 elsewhere in the room.

Can I put downlights over a shower?

Yes, if they are rated for zone 1. Choose a sealed IP65 downlight, and a fire rated one if there is a room or loft above.

Is IP44 good enough for a bathroom?

IP44 meets the minimum for zones 1 and 2 where no water jets are used, and suits zone 2 and outside the zones well. Directly over a shower, IP65 gives more protection against direct spray and steam.

Do bathroom lights need to be 12V?

Not usually. Mains lights are allowed in zones 1 and 2 if they have the right IP rating and are made for the zone. Only zone 0 requires SELV, with the transformer outside the zones.

Where can a light switch go in a bathroom?

A standard wall switch must be outside the zones, usually outside the door. Inside the room, use a ceiling pull cord switch.

Can I fit a bathroom light myself?

Changing a lamp is fine. Adding, moving or replacing a fixed light in a bathroom is usually notifiable work under Part P in England and Wales, so use a registered electrician.