Emergency Lighting Explained: Maintained vs Non-Maintained, Testing and the Rules

11 min read

Office stairwell with LED emergency bulkheads and an illuminated exit sign above the door

The short answer

Emergency lighting switches on from a battery when the normal lighting fails, so people can find their way out. Non-maintained fittings light only in a power cut; maintained fittings are on all the time and stay on. Most UK fittings are rated for 3 hours. Test every fitting monthly with the key switch, have a competent person do a full duration test every year, and record each test in a logbook.

Key takeaways

  • Non-maintained: off normally, on in a power cut. Maintained: on all the time, stays on in a power cut. Exit signs are usually maintained.
  • If people need artificial light to find their way out, the premises needs emergency escape lighting; the fire risk assessment sets the layout.
  • Three hours is the usual rating in the UK; all the fittings and packs in our emergency range are 3 hour.
  • Test monthly with the key switch, have a competent person do a full duration test every year, and keep a logbook.
  • Every emergency fitting needs an unswitched live to charge its battery, or it will fail its test.
On this page
  1. What is emergency lighting?
  2. Maintained or non maintained emergency lighting?
  3. 1 hour or 3 hour emergency lighting?
  4. Where is emergency lighting needed?
  5. Emergency lighting testing: monthly and annual
  6. Types of emergency light and when to use them
  7. If you want the short version
  8. Common questions

What is emergency lighting?

Emergency lighting is lighting that keeps working when the normal lighting fails. Each fitting has its own battery, or is fed from a central battery system, and switches over automatically in a power cut. Its first job is to let people find their way out safely: along corridors, down stairs, through exit doors, past changes of level.

You will meet three terms:

  • Emergency escape lighting: lights the escape routes and exits, the open areas people cross to reach them, and any high risk task areas where a process has to be shut down safely. This is what most buildings need.
  • Exit signs: illuminated signs with the running man symbol and an arrow, so the way out can be seen in smoke or darkness.
  • Standby lighting: enough light for normal activity to carry on in a power cut, for example in a hospital or a control room. It is a design choice, not a minimum.

Maintained or non maintained emergency lighting?

This is the question most people search for, and the answer is simple once you see it on a timeline.

When the mains fails, normal lights go out, non-maintained emergency lights come on, and maintained emergency lights stay on Mains onPower cut Normal lighting Non-maintained Maintained litoffon battery for the rated time
Non-maintained fittings are off while the mains is healthy and only light in a power cut. Maintained fittings are lit all the time and keep going on battery when the mains fails.
Non-maintained Maintained
Normal operation Off. A small indicator shows the battery is charging On, as a normal light
In a power cut Switches on from the battery Stays on, now from the battery
Typical use Corridors, stairs and open areas that have normal lighting when occupied Exit signs, and places where the normal lights may be dimmed or off while people are inside, such as cinemas, theatres and bars
Supply needed Permanent (unswitched) live to charge the battery Permanent live, plus a switched live if the fitting is switched with the room lights
Energy use Only the charger The lamp all the time, plus the charger

What is a non maintained emergency light?

A fitting that does nothing visible until the power fails. It sits next to the normal lighting, keeps its battery charged from a permanent live, and lights up only when that supply is lost. Most emergency bulkheads, twin spots and recessed emergency spots in corridors and stairwells are non-maintained. Our Knightsbridge twin spot and Liteplan recessed spots are examples.

What is maintained emergency lighting?

A fitting that works as a normal light and also as an emergency light. Exit signs are the classic case, because the sign must be readable whenever people are in the building. Our ceiling mounted exit sign runs in maintained mode for 3 hours on its battery.

Converted fittings: your normal light becomes an emergency light

The neatest solution in offices, plant rooms and warehouses is often to add an emergency pack to a normal fitting, so you do not need extra fittings on the ceiling. The light works from its wall switch as usual, and if the mains fails it runs from its own battery. These need two supplies: a permanent live to keep the battery charged, and the switched live for normal use. Our Liteplan conversion packs work this way, and we sell T8 tube kits with the pack already matched.

Get this right

Every emergency fitting needs an unswitched live to charge its battery. If it is wired to the switched live only, the battery drains every time someone turns the lights off, and the fitting will report a fault or fail its test.

1 hour or 3 hour emergency lighting?

Emergency fittings are rated for how long they light on battery, usually 1 hour or 3 hours. Three hours is the common choice in the UK, because it covers buildings where people may stay inside during a power cut or come back in before the batteries have recharged, such as anywhere people sleep. One hour can be acceptable in some premises where everyone leaves straight away and the building is not reoccupied until the system has recharged.

Which you need is decided by the fire risk assessment and the lighting designer, not by the shop. All the fittings and packs in our emergency range are rated for 3 hours, which suits both cases.

Remember recharge time too. Our Liteplan packs and the Halo spot take 24 hours to recharge fully after a discharge. Until then the system cannot give its full rated time.

Where is emergency lighting needed?

In short: anywhere people would need artificial light to find their way out. For most workplaces, shops, offices and the common parts of shared buildings in England and Wales, the law is the Regulatory Reform (Fire Safety) Order 2005. Article 14 says emergency routes and exits that need illumination must have "emergency lighting of adequate intensity" in case the normal lighting fails.

The government's guide for small non-domestic premises puts it in plain terms: if you need artificial lighting to see your way out, you must have emergency escape lighting. It also says that many small ground floor premises with enough borrowed light from outside, such as street lighting, will not need it. Where it is needed, it should light exit doors and exit routes, including staircases, corridors and areas without natural light, such as basements.

Designers usually also put an emergency light near the points where people need to see something in a hurry:

  • each exit door, and outside it if the route continues outdoors
  • every staircase, so each flight is lit
  • changes of direction and changes of floor level
  • fire alarm call points and firefighting equipment
  • first aid points
  • exit signs and safety signs

The exact layout comes from the fire risk assessment and the design. The responsible person under the Fire Safety Order, usually the employer, or whoever controls or owns the premises, is responsible for making sure it is provided and kept working.

The British Standard

The UK code of practice is BS 5266-1, Emergency lighting of premises. BSI published a new edition, BS 5266-1:2025, which now also covers standby lighting and local area lighting alongside escape lighting, and is aligned with the European standards EN 1838 and EN 50172. It is a code of practice, so it gives recommendations rather than being law itself, but it is what designers, installers and fire risk assessors work to. If your system was designed to an older edition, your assessor or installer can advise whether anything needs to change.

Homes, HMOs and blocks of flats

An ordinary single family home does not normally need emergency lighting. Houses in multiple occupation (HMOs) and the common parts of blocks of flats are different: councils set HMO standards, and many expect emergency lighting on the escape route in larger or higher risk HMOs. Check your local council's HMO standards and your fire risk assessment. Landlords searching for an emergency light for a hallway or stairwell usually want a non-maintained bulkhead or a converted ceiling light, plus a monthly test routine.

Emergency lighting testing: monthly and annual

An emergency light that has never been tested cannot be trusted. The battery is the part that wears out, and you only find out it has failed during a test or a real power cut. The government's guide says a functional test of all emergency escape lighting should be done monthly, and that it should be inspected and tested by a competent contractor every year.

Test How often What happens Who
Functional test (flick test) Monthly Simulate a mains failure with the test key switch for a short time; walk round and check every fitting lights The responsible person or someone they appoint
Full duration test Yearly Simulate a mains failure for the full rated time (3 hours for a 3 hour fitting) and check every fitting stays lit to the end A competent person, usually an electrician or emergency lighting contractor
Recharge check After every test Restore the supply and check every charge indicator is back on Whoever did the test

How to test emergency lighting (the monthly flick test)

  1. Choose a quiet time, and tell occupants the lights are being tested.
  2. Turn the emergency lighting test switch with its key. This cuts the supply to the emergency fittings only, so the normal lighting and other circuits stay on.
  3. Walk the whole route. Every non-maintained fitting should light, and every maintained fitting should stay lit.
  4. Keep the test short. A long monthly test drains the batteries and leaves the building less protected until they recharge.
  5. Turn the key back and check each charge indicator shows the battery is charging again.
  6. Write it in the logbook: date, result, any fitting that failed, and what was done about it.

The annual full duration test drains the batteries completely, so plan it for a time when the building can be left without full emergency cover while they recharge, for example the start of a weekend in an office. That is another reason to choose fittings that recharge within 24 hours.

The emergency lighting test switch

The test switch, often called a fish key switch after the shape of its key, is fitted next to the distribution board or in a common area. It interrupts the permanent live feeding the emergency fittings on that circuit without turning off the normal lights. Never test by switching off the main switch at the consumer unit: it leaves people in the dark, and can switch off equipment that needs to stay on.

Self testing emergency lights

Self-test fittings run their own short functional tests and duration tests on a timer and show the result on an indicator. Our Halo emergency spot has auto self-test with a battery failure warning, the Knightsbridge twin spot and Olympia Power Light twin spot both self-test, and the Liteplan DNA DALI packs report to a DALI control system or revert to standalone self-test. Self-test saves time on the walk round, but someone still needs to check the indicators each month and record the results.

Types of emergency light and when to use them

Type Where it goes From our range
Exit sign Above or near every exit and along the route, with an arrow showing the direction Ceiling mount LED exit sign, arrow down, 3 hour maintained
Twin spot Warehouses, plant rooms, car parks and large open areas Knightsbridge 2x3W twin spot, IP65, self-test; Olympia Power Light, 1760 lm
Recessed emergency spot Offices, shops and corridors with suspended or plasterboard ceilings, where it should be discreet Liteplan spots with flood or corridor lens, 40 to 43mm cut-out; Halo spot, surface or recessed
Emergency bulkhead Stairwells, entrances, outside exit doors Nova bulkheads with emergency option, 180 lm for 3 hours
Converted tube or lamp Existing batten, tri-proof or 2D fittings, so no extra fittings are needed T8 emergency tube kits in 2ft, 4ft, 5ft and 6ft; PLG24 emergency kits
DALI emergency pack Buildings with DALI lighting control and central monitoring Liteplan DNA/1 and DNA/2, addressable, self-test

A note on converting lamps: not every LED lamp or fitting is suitable for an emergency pack, because the pack has to drive the LEDs directly. Liteplan has tested its NLP/1S/80-K pack with our T8 and T5 tubes, GU10 spots and GLS bulbs. For other fittings, such as an LED panel, send us the model and we will check which pack, if any, suits it.

Safety: when to call an electrician

Installing emergency lighting, adding an emergency pack to a fitting, or fitting a test key switch is electrical work and should be done by a qualified electrician, who can also certify the installation. In England and Wales some domestic electrical work must be notified under Part P of the Building Regulations. The system design and the annual test should be done by a competent person, and the layout should follow your fire risk assessment.

For installers

  • Liteplan NLP/1S/80-K: 3 hour, LED load 6 to 80V, rated LED current 385mA to 32mA, 3.2V 4.8Ah LiFePO4, 24 hour recharge, module 178 x 30 x 22.5mm (172mm centres), push wire terminals 0.5 to 1.5mm². Needs an unswitched supply for charging and the switched supply for normal use.
  • Liteplan NLP/1 TP40: remote mounting kit, maintained or non-maintained, LED 6 to 55V, 2 to 20 LEDs in series, 40mm aperture or greater.
  • Liteplan recessed spots: S-HLP/1/LED/43 flood or corridor lens, 40 to 43mm cut-out, wired in series through the C4201 plug; S/BNM/1 needs a 90mm void.
  • Knightsbridge EMTWINST: 2x3W, 490 lm in emergency, IP65, non-maintained, self-test, Class II, Ni-Cd battery.
  • Exit sign: 6W LED, 3 hour maintained, 3.6V 1.5Ah Ni-Cd, test button underneath, 30m viewing distance, BESA box fixing.

If you want the short version

Non-maintained fittings only light in a power cut; maintained fittings are on all the time and stay on when the mains fails. Most corridors and stairs use non-maintained, exit signs are usually maintained, and converting existing fittings with a battery pack avoids extra fittings. Choose 3 hour unless your fire risk assessment says otherwise. Test monthly with the key switch, have a competent person do a full duration test every year, and record every test in the logbook.

Products that help

See all LED Emergency Lighting · See all T8 LED Tubes · See all PLG24 · How to Replace a Fluorescent Tube with LED: the Ban, Starters and Ballast Bypass · Garage Lighting Guide: LED Battens, Lumens and How Many You Need · LED High Bay Lighting: UFO vs Linear, Lux Levels and Payback for Warehouses

Common questions

What is a non maintained emergency light?

A light that stays off while the mains is healthy and switches on from its own battery when the power fails. It needs a permanent live to keep the battery charged.

What is the difference between maintained and non-maintained emergency lighting?

Maintained fittings work as normal lights and stay on from the battery in a power cut. Non-maintained fittings are off in normal use and only light when the mains fails.

How often should emergency lighting be tested?

The government's fire safety guide says a functional test of all emergency escape lighting should be done monthly, and that it should be inspected and tested by a competent contractor every year. The annual test is normally a full duration test.

How long should emergency lighting last?

Fittings are rated for 1 hour or 3 hours on battery. Three hours is the common choice in the UK; the fire risk assessment and the designer decide what a building needs.

What is emergency lighting installed to illuminate?

Escape routes and exits, including stairs, corridors and exit doors, plus areas without natural light. Designers also light fire alarm call points, firefighting equipment, first aid points, changes of level and exit signs.

Do I need emergency lighting in my house?

An ordinary single family home does not normally need it. HMOs and the common parts of blocks of flats often do, depending on the fire risk assessment and the local council's HMO standards.

Can I convert an existing light into an emergency light?

Often, yes, by fitting an emergency battery pack inside it, but not every LED lamp or fitting is suitable. The work should be done by a qualified electrician, and the fitting needs both a permanent and a switched live.