DALI Lighting, 0-10V and 1-10V Dimming Explained for Installers

10 min read

Modern UK open plan office with recessed LED panels dimmed in zones and a glass touch control panel on the wall

The short answer

DALI is a digital lighting control system where every driver on a two wire bus has its own address, so lights can be switched, dimmed, grouped and monitored one by one: up to 64 per line, with 16 groups and 16 scenes. 1-10V and 0-10V are simpler analogue controls on a polarised pair that set one level for every driver and need the mains switched to turn off. TRIAC dims through the mains and suits homes.

Key takeaways

  • TRIAC for domestic dimmer switches, 1-10V or 0-10V for single commercial zones and sensors, DALI for groups, scenes, schedules and monitoring.
  • 1-10V: polarised control pair, passive dimmer, 1V is minimum not off, so switch the mains.
  • DALI: 16V bus from a bus power supply, two cores with no polarity at the driver, up to 64 addresses per line and 300m of cable.
  • DALI-2 brings sensors and controls into the standard; DT8 drivers give tunable white.
  • Match every driver to its control type, and treat control cores as mains when wiring.
On this page
  1. What is DALI lighting?
  2. DALI vs 1-10V vs 0-10V vs TRIAC: the differences
  3. What is 1-10V dimming?
  4. How does DALI work?
  5. DALI-2, DT8 and tunable white
  6. Sensors, push switches and converters
  7. When is a TRIAC dimmer enough?
  8. Which Ledison part do I need?
  9. The short version
  10. Common questions

What is DALI lighting?

DALI lighting is a digital lighting control system where every driver on a two wire bus has its own address, so you can switch, dim and group lights one by one from a controller. DALI stands for Digital Addressable Lighting Interface. It is an international open standard, published as IEC 62386, so drivers, sensors and controls from different makers work together. Unlike simple dimming, it talks both ways: a controller can ask a driver its level, its status, or whether its lamp has failed.

DALI is one of four ways to dim LED lighting you will meet on a job. The other three are 1-10V, 0-10V and mains TRIAC dimming. This guide explains each, how to wire it, and when each is the right choice.

DALI vs 1-10V vs 0-10V vs TRIAC: the differences

TRIAC (phase cut) 1-10V 0-10V DALI and DALI-2
Signal Chops the 230V mains Analogue DC, driver sources, dimmer sinks Analogue DC, usually from a powered controller Digital, on a 16V DC bus
Extra wires None Two control cores Two control cores Two bus cores
Polarity Not applicable Matters Matters Not polarity sensitive at the driver
Off Dimmer switches off Needs a switch or relay on the mains; 1V is minimum, not off Some drivers dim to off at 0V, others need a relay Off by command; mains stays on
Control of each light All lights on the dimmer together All drivers on the control pair together All drivers on the control pair together Each light, group or scene separately
Feedback None None None Yes: level, status, lamp failure
Typical use Homes, single rooms Commercial zones, sensors, high bays LED strip, controllers, sensors Offices, schools, hospitals, warehouses, whole buildings

The rule of thumb: TRIAC for a dimmer switch on a domestic circuit, 1-10V or 0-10V for one zone or a sensor in a commercial space, DALI when you want lights grouped, scened, scheduled or monitored, or when the layout may change later.

What is 1-10V dimming?

1-10V is an analogue control where the voltage on a separate pair of wires sets the light level: 10V is full brightness and 1V is the minimum. In a true 1-10V system the driver supplies a small current onto the control pair and the dimmer, which is in effect a variable resistance, pulls the voltage down. That is why the dimmer needs no power of its own, and why it is called passive.

How to wire 1-10V

  • Two circuits. The mains supply (live, neutral, earth) goes to each driver through a switch or relay. The control pair (+ and -) runs from the dimmer to the 1-10V terminals of every driver.
  • Polarity matters. Connect + to + and - to - on every driver. A reversed pair usually means no dimming or the lights stuck at minimum.
  • 1V is not off. At the bottom of the range the lights sit at their minimum level. To turn them off you switch the mains. Our Osram DIM MCU 1-10V rotary dimmer has a push on/off switch with a 6A contact for this.
  • Count the drivers. Every driver puts a little current onto the control pair, and the dimmer can only sink so much. The Osram DIM MCU is rated at 40mA on its control output and controls up to 50 dimmable drivers. Check the figure for your dimmer and drivers.

What is 0-10V dimming?

0-10V works the same way but goes down to 0V, and the signal usually comes from a powered controller rather than a passive dimmer. The names are often mixed up, and many products accept both. The practical differences are that some 0-10V drivers dim right down to off, and that an active controller can drive only a set number of drivers. Our T18 touch glass 0-10V dimmer, for example, gives a 20mA output, recommends no more than five drivers, and has a relay output of up to 1.5A to switch the mains. If you mix a passive 1-10V dimmer with a driver that expects an active 0-10V signal, it will not dim, so check both data sheets.

How does DALI work?

A bus power supply puts about 16V DC onto a two core bus, and a controller sends digital commands down it to drivers that each have an address.

  • Up to 64 addresses per DALI line. Each driver or control gear gets one address. For more than 64, add another line. Our Easeic DBC202D bus management module runs two lines of 64 from one DIN rail unit.
  • Groups and scenes. Drivers can be put into up to 16 groups, and up to 16 scene levels can be stored, so one button can set a whole room to "presentation" or "cleaning".
  • Bus power. Every DALI line needs a bus power supply, either separate or built into the controller. Our Euchips DALI-130 gives 16V at 250mA and our Glacial GP-DP004N gives 16V at 200mA for up to 64 DALI lights. Each driver draws only a small current from the bus: the spec tables of our Easeic drivers list a DALI sink current below 2mA.
  • Cable length. Keep a DALI line within 300m in total. Our Euchips bus supply and Osram DALI MCU both list up to 300m. Use a cable size that keeps voltage drop on the bus low over long runs.
  • No polarity at the driver. The two DA terminals on a DALI driver can be connected either way round, which makes looping between fittings quick. Bus power supplies and some controls are marked, so follow their labels.
DALI wiring: mains to every driver plus a two core bus from the bus power supply and controller, compared with 1-10V wiring where a dimmer feeds a polarised control pair and switches the mains DALI 1-10V bus power andcontroller 1-10V dimmerwith mains switch driver 1driver 2driver 3 driverdriverdriver mains L N E, always live switched mains L N E DA DA bus, either way round + and - control pair, polarity matters each driver has its own address up to 64 per line, 16 groups, 16 scenes off is a command, not a switch every driver follows one level 1V is minimum, not off the dimmer switches the mains to turn off
Simplified wiring. With DALI the mains feeds every driver permanently and the two bus cores carry all the switching and dimming. With 1-10V the dimmer sets one level for every driver on the pair and switches the mains to turn them off. Always follow the driver and control instructions.

Addressing and commissioning

Out of the box, DALI drivers have no address. A simple DALI rotary or push button control can work in broadcast mode, sending every command to every driver on the line, which is fine for one room with no zones. To use groups and scenes you commission the line: the controller finds each driver, gives it an address and puts it in its groups. Our Euchips DALI-200 master controller does this from a computer over USB, and the Easeic DBC202D module has an LCD for setting up on site. Label each fitting with its address as you go: it saves hours when someone comes back to change a scene.

DALI-2, DT8 and tunable white

DALI-2 is the newer generation of the standard. It tightens the rules for drivers and brings sensors, push buttons and controllers into the standard too, with certification so that parts from different makers work together. Original DALI covered mainly the drivers, so sensors and switches from one brand did not always work with another's controller. Look for DALI-2 on new projects, especially where you want to mix brands. Several of our drivers are DALI-2, including most of the Easeic LND series and the Boke BK-DUL042.

DT8 stands for device type 8, the part of DALI that controls colour. The common use is tunable white: warmer light in the evening, cooler in the working day, from one fitting. You need DT8 or tunable white drivers, fittings with two LED channels, and a control that sends colour commands. Our Osram DALI MCU TW G2 is a rotary tunable white control for up to 25 drivers.

Sensors, push switches and converters

  • Push switch control. Our Euchips DALI-GSC-4 sits in a switch back box behind ordinary push switches and controls 4 groups or 4 scenes. Many of our DALI drivers also accept push dim directly from a mains retractive switch, which is the simplest dimming of all for a single room.
  • Scene panels. The Euchips DALI-P02 glass touch panel controls 3 groups and 4 scenes, in black or white, and fits many standard back boxes.
  • Bringing analogue onto DALI. The Glacial LDN-DA02 converts a DALI address into a 0-10V, 1-10V or PWM signal with a relay, so LED strip drivers or analogue high bays can join a DALI system.
  • Sensors on 1-10V. Where a full DALI system is not justified, a 1-10V sensor gives step dimming in corridors and aisles, such as the Merrytek MC054V microwave and daylight sensor on our Attica trunking.

When is a TRIAC dimmer enough?

In most homes. If you only want to dim one room from the wall, a good trailing edge LED dimmer switch and dimmable lamps or TRIAC drivers do the job with no extra wiring. Move to 1-10V or DALI when you need several zones, sensors, scenes, emergency monitoring, or control of large commercial loads. If TRIAC dimmed LEDs flicker or hum, see why LED lights flicker, buzz or glow.

Which Ledison part do I need?

Job Part Key facts from the spec table
Power a DALI line Euchips DALI-130 or Glacial GP-DP004N-16V 16V, 250mA, DIN rail or screw fixing, 300m; or 16V, 200mA, up to 64 lights
Run and commission two DALI lines Easeic DBC202D 2 x 64 addresses, 2 x 250mA bus power, LCD, DIN rail
Commission from a laptop Euchips DALI-200 USB master controller, IEC 62386
DALI-2 driver that also does 1-10V Easeic LND118 to LND154BL 18W to 54W, CC, DALI-2, 1-10V, PWM and push dim
DALI driver for panels and downlights Euchips EUP20D, EUP30D, EUP60D or Mean Well LCM-25DA CC, selectable output current, DALI and push dim
1-10V driver Euchips EUP A series or Easeic LNA series CC, 10W to 60W, 0/1-10V, PWM, resistance
1-10V rotary dimmer Osram DIM MCU Push on/off, 40mA control output, up to 50 drivers, 6A switch
0-10V wall dimmer for strip or drivers T18 touch glass or KL rotary 0/1-10V output, relay output, optional RF remote
Tunable white Osram DALI MCU TW G2 Rotary, DALI edition 2, up to 25 drivers

Browse the full ranges: DALI drivers and controls and 1-10V drivers and dimmers.

Safety: when to call an electrician

DALI, 1-10V and 0-10V control systems are installed alongside mains wiring and should be designed and fitted by a qualified electrician. On many drivers the control terminals are separated from the mains by basic insulation only, so treat the control cores as if they were live: use cable rated for mains voltage, follow the driver instructions on running control and mains cores together, and isolate the circuit before working on any part of it. Remember that a DALI fitting switched off by command is still connected to live mains.

Get this right

Match every part to the same control type. A DALI driver needs a DALI bus and controller, a 1-10V driver needs a 1-10V dimmer or controller, and a mains dimmer dims neither. Drivers that accept several signals, such as our Easeic LND118 to LND154BL, keep your options open if the plan changes.

For installers

  • Bus budget: add up the bus current of every device (drivers below 2mA each on our Easeic spec tables, controls such as the DALI-200 and DALI-GSC-4 at 2mA) and keep it within the bus supply's rating, 200mA or 250mA on our units.
  • Philips Xitanium 36W TD: DALI, Touch and Dim and corridor mode, 0.15A to 1.05A, 24 to 54V, DC emergency dimming.
  • Boke BK-DUL042: 42W, up to 1100mA in 16 DIP steps, DALI-2, push dim and 1-10V, central and self-contained emergency supported.
  • Euchips EUP D series: 20W and 30W DALI with push dim, dimming range 0.1% to 100% and dim to off; 60W version at 1050mA to 1400mA.
  • Emergency: DALI can monitor emergency fittings on the same bus as the general lighting, with suitable emergency control gear.

The short version

TRIAC dims through the mains and suits homes. 1-10V and 0-10V use a separate polarised control pair, set one level for every driver on it, and need the mains switched to turn lights off. DALI puts every driver on a two wire digital bus with its own address: up to 64 per line, 16 groups and 16 scenes, with feedback and no polarity at the driver. Use DALI-2 parts on new jobs, DT8 drivers for tunable white, and match every driver to its control. Have it designed and installed by a qualified electrician.

Products that help

See all DALI Dimmable Drivers · See all LED Drivers 1-10V · See all LED Dimmer Switches · LED Drivers Explained: Constant Voltage vs Constant Current, and How to Size One · Dimmer Switch for LED Lights: Trailing Edge, Minimum Load and How Many Lamps · LED High Bay Lighting: UFO vs Linear, Lux Levels and Payback for Warehouses

Common questions

What is DALI lighting?

DALI, the Digital Addressable Lighting Interface, is an open digital lighting control standard (IEC 62386). Each driver on a two wire bus has its own address, so lights can be dimmed and switched individually or in groups.

What is the difference between DALI and 1-10V dimming?

1-10V is analogue: one control pair sets one level for every driver on it, with no feedback. DALI is digital: each driver is addressed separately, can be grouped and scened, and reports its status.

Does DALI need a bus power supply?

Yes. Every DALI line needs about 16V DC from a bus power supply, either a separate unit or one built into the controller. Ours give 200mA or 250mA.

Is DALI polarity sensitive?

Not at the driver: the two DA terminals can be connected either way round. Bus power supplies and some controls are marked, so follow their labels.

How many DALI drivers can go on one line?

Up to 64 addresses per line, within the bus supply's current. For more, add another line or a multi-line controller.

What is the difference between 0-10V and 1-10V?

Both use a DC control pair. 1-10V is usually passive, with the driver supplying the current and 1V as the minimum. 0-10V usually comes from a powered controller and some drivers dim to off at 0V. Check both data sheets.

What is DALI DT8?

Device type 8 is the colour control part of DALI, most often used for tunable white fittings that change from warm to cool white.